. IFS-2600 Fire Indicator Panel TECHNICAL, PROGRAMMING & INSTALLATION MANUAL 3.01 8/05/08 Rev: P/N 10069 ECN08-0066. Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Documentation Feedback Your feedback helps us keep our documentation up to date and accurate.
If you have any comments or suggestions about our printed manuals you can email us. Please include the following information: Product name and version number (if applicable) . IFS-2600 Installation & Programming Manual COMPATIBLE DETECTORS.5 OVERVIEW.6 CAUTION. 6 SPECIFICATION.7 APPROVALS. 7 ENVIRONMENTAL LIMITS. 7 POWER SUPPLY RATINGS AND SETTINGS.
9 INTERNAL 24 VDC (nom) 3.0A MAIN POWER SUPPLY. 9 INTERNAL 27.3V DC 1.5A BATTERY CHARGER. 9 Internal 5VDC 2A Power Supply. Page 2 PCB2005 TERMINATION BOARD. 14 INTERNAL 5VDC POWER SUPPLY TP8. 14 POWER SUPPLY COMPARATOR REFERENCE VOLTAGE TP10. 14 NON ADJUSTABLE TEST POINTS.
14 ALARM THRESHOLD COMPARATOR TP7. 15 FAULT THRESHOLD COMPARATOR TP6. 15 CONFIGURATION JUMPERS. 16 IFS2004 - JP3 DEFAULT. IFS-2600 Installation & Programming Manual MAIN MENU.
30 EXIT PROGRAMMING MODE. 31 ZONE PROGRAMMING. 31 SELECT ZONE #. 31 ZONE SELECTED.
31 ZONE TYPE. 31 ZONE OUTPUT CONFIGURATION. 32 RELAY PROGRAMMING MODE. 32 SELECT RELAY #. 32 RELAY SELECTED. Page 4 APPENDIX F.
43 GLOSSARY OF TERMS. 43 APPENDIX G.
44 SUMMARY OF TERMINATIONS AND CAUTIONS. 44 DETECTION ZONES. 44 RELAY OUTPUTS. 44 BELL OUTPUTS. 44 ACF OUTPUTS.
44 WARNING SYSTEM. 44 DOOR HOLDER OUTPUTS. IFS-2600 Installation & Programming Manual Make Model System Sensor Thermal System Sensor Thermal System Sensor Thermal System Sensor Thermal System Sensor Thermal System Sensor Thermal System Sensor Thermal System Sensor Smoke System Sensor Smoke System Sensor Smoke System Sensor Thermal System Sensor Smoke System Sensor.
Page 6 IFS-2600 Fire Indicator Panel (FIP) is designed to provide simplicity to the end user. The FIP uses both a liquid crystal display and conventional LED displays for fast and accurate display of system status and changing events. A custom designed membrane keypad is used together with the liquid crystal display and LED indicators to provide fast, efficient and simple modes of operation.
IFS-2600 Installation & Programming Manual Cabinet Outside Dimensions AC Operational Voltage Internal Power Supplies Microprocessor Memory Type Liquid Crystal Display Fuses E.O.L Resistor On AZFs, monitored outputs, Bells, Warning system, ACF APPROVALS Australian Standard AS4428.1 1998 SSL Approval No AFP-1553 C-Tick Approval No. Page 8 SYSTEM EXPANSION Zones Hardware Required Main Control Board Main Termination board Power Supply board Main Control board Main Termination board Power Supply board 8 Zone Expansion board 16 Zone Indicator board Main Control board Main Termination board Power Supply board 8 Zone Expansion board 16 Zone Indicator board Main Control board. IFS-2600 Installation & Programming Manual POWER SUPPLY RATINGS AND SETTINGS INTERNAL 24 VDC (nom) 3.0A MAIN POWER SUPPLY This supply's primary function is to power panel logic and all external operations of the FIP, i.e.: detection circuits, ancillary circuits, etc. This supply meets the requirements of AS4428.5.
AC Input Output Current Output Voltage. Page 10 EXTERNAL 27VDC POWER SUPPLY This supply is used in addition to the internal power supply for large systems. Its primary function is to power any additional ancillary loads of the FIP up to 7 amps.
This supply meets the requirements of AS4428.5 Important Notes: When using external power supply, JP1 link on IFS2006E must be fitted to enable external PSU monitoring. IFS-2600 Installation & Programming Manual GENERAL The IFS-2600 in its most basic form comprises of three boards, the main control board, the main termination board and the power supply board. The main control board contains the Microprocessor, EPROM, RAM and E has the liquid crystal display and keypad attached. Page 12 AZF DESCRIPTION The AZF's on the IFS-2600 are monitored and scanned by custom thick film hybrids. These hybrid IC's significantly reduce the possibility of false alarms and improve product efficiency and reliability. The total Alarm Zone loop resistance is the sum of the end of line resistor (EOLR 4K7) plus all the parallel connected detector loads. IFS-2600 Installation & Programming Manual PRINTER OUTPUT The printer port is designed to be used during testing and commissioning of the panel.
The serial printer will report alarms and faults together with the date and time of the event. “walk test” mode to produce a history of the test and can also be used to print current programming configuration. Page 14 PCB2006 POWER SUPPLY BOARD INTERNAL 24VDC (nom) POWER SUPPLY With batteries disconnected and no alarms present, measure voltage across the 0V and MAIN test points on the 2006 power supply board and, if necessary, adjust the multi-turn potentiometer VR2 until voltage is 26.5V 0.05V (26.45V –. IFS-2600 Installation & Programming Manual ALARM THRESHOLD COMPARATOR TP7 With the panel in the quiescent mode, measure and take note of the INTERNAL 24V DC POWER SUPPLY as above. Measure voltage between system 0V and TP7.
Adjust multi-turn potentiometer VR4, and adjust until the voltage is as per the following table. Page 16 CONFIGURATION JUMPERS IFS2004 - JP3 DEFAULT Holding a short across these pins for 5 seconds during start-up causes the panel to reset to standard factory defaults. The panel will give 4 beeps after reset, to acknowledge default on start-up. IFS2004 - JP4 PROGRAM DISABLE When fitted, jumper between these pins to inhibit program changes.
IFS-2600 Installation & Programming Manual Suitably qualified technicians must install the panel. The following check procedures are recommended after every installation and prior to initial power-up. A thorough visual inspection should be made to every aspect of the fire panel. This includes loose wire, metal filings, loose circuit boards, loose cabling, damage in transit etc.
Page 18 POWER UP CHECKLIST Ensure batteries are disconnected. Turn mains switch to 'on' The 'mains on' led should light. Allow 15 seconds for the panel to perform its start up tests. Connect batteries FUNCTIONAL TESTING . IFS-2600 Installation & Programming Manual Page 19 FAULT RECORD FAULT CORRECTION DATE TESTS SATISFACTORILY COMPLETED. TESTED BY SIGNATURE DATE OF TEST If all faults have been rectified and all tests are completed satisfactorily, the 2600 fire indicator panel is now ready for operation.
Page 20 INDICATORS Descriptor Colour MAINS ON Green BATTERY Yellow FAULT PSU FAULT Yellow CHARGER Yellow COMMON Yellow FAULT ACF ACT ACF FLT Yellow ACF ISO Yellow Bell ACT Bell FLT Yellow Bell ISO Yellow Warning System ACT Warning Yellow System FLT Warning Yellow. IFS-2600 Installation & Programming Manual SUGGESTED ALARM PROCEDURE The following is a suggested alarm procedure for use by building fire officers or duty wardens. The fire indicator panel is designed for use by qualified fire fighters and it is strongly recommended that the fire panel not be operated in an emergency situation by anyone other than suitably qualified fire fighters. Page 22 BELL ISOLATE Depressing the 'EXT BELL ISOLATE' key will isolate the bells. The 'Ext Bells Isolate' LED will illuminate and the bells will not sound until the bells are de-isolated. Pressing 'EXT BELL ISOLATE' a second time will de- isolate the bell. IFS-2600 Installation & Programming Manual WALK TEST MODE This function will place the panel into 'walk test' mode.
Walk test mode is used for the on-site testing of detector zones. This mode cannot be selected if any zone(s) is in alarm.
Entry to walk test mode will be acknowledged by three beeps and the LCD will display 'WALK TEST MODE'. Page 24 IFS-2600 Installation & Programming Manual ZONE FUNCTIONS Zone functions are those relating specifically to the detection zones. Following is an explanation of their operation and the keystrokes required to perform the function required.
ALARM TEST ALARM TEST The alarm test function momentarily disconnects the detector lines of the zone(s) under test and simulates a detector going into alarm, therefore testing the zone(s) alarm detection capability. IFS-2600 Installation & Programming Manual FAULT TEST The fault test function momentarily disconnects the detection zone(s) under test and simulates the worst-case condition for fault.
A resistor load equal to worst case fault is placed on the zone continuously for 5 seconds then the zone is returned back to its normal condition. Page 26 ISOLATE The isolate function prevents the transmission of alarms or faults from the zones, to the master alarm facility. ‘#’ in the above key sequence is the zone number.
If only one zone is to be isolated, use the appropriate zone number. Alternatively the 'ALL' button can be used to simultaneously isolate all zones. IFS-2600 Installation & Programming Manual GLOBAL OPTIONS ZONE OPTIONS Type Output Description Indicate Only Indicate, Bell Indicate, Bell, General Alarm Indicate, Bell, General Alarm, Ancillary Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1 Indicate, Bell, General Alarm, Ancillary Brigade Relay #2 Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1, &. Page 28 OUTPUT RELAY OPTIONS Optional Relays can be programmed to simulate: - Isolate Relay ACF Output Brigade Relay #1 Brigade Relay #2 Fault Relay Mains Fail Relay General Alarm Relay Bell Output . IFS-2600 Installation & Programming Manual PROGRAM MODE Press the following buttons in order shown to enter programming mode. → PREVIOUS NEXT PROGRAMMING MODE The liquid crystal display will display all messages and prompts required to program the 2600.
ONLY the 'PREVIOUS','NEXT','SELECT','EXIT' AND 'ENTER' keys are used in programming mode. All other keys will give an error beep and are ignored.
Page 30 RELAYS TYPE ISOLATE RELAY ANCILLARY OUTPUT (ACF) BRIGADE RELAY #1 BRIGADE RELAY #2 FAULT RELAY MAINS FAIL RELAY GENERAL ALARM RELAY BELL OUTPUT DOOR HOLDER RELAY MAP - AND MAP - OR MAP - FAULT MAP – ISOLATE MAP –. IFS-2600 Installation & Programming Manual EXIT PROGRAMMING MODE Use the 'NEXT' & 'PREVIOUS' keys to scroll through 'YES' & 'NO'. Once the desired option has been highlighted, pressing the 'SELECT' button will select it. Highlighting 'YES' and pressing 'SELECT' will write all changes made to the system memory (E the panel will then restart. Page 32 Once the desired option has been highlighted, pressing the 'SELECT' button will select it. Making a selection or pressing 'EXIT' will return to zone selected.
Note: The option previously set is displayed in brackets and is the first to be displayed. Previously set options will not be displayed if 'ALL'. IFS-2600 Installation & Programming Manual RELAY TYPE Use the 'NEXT' & 'PREVIOUS' keys to scroll through: Once the desired option has been highlighted, pressing the 'SELECT' button will select it.
Making a selection or pressing 'EXIT' will return to 'Relay Selected'. Note: The option previously set is displayed in brackets and is the first to be displayed. Page 34 ACF OUTPUT Use the 'NEXT' & 'PREVIOUS' keys to scroll through: Note: The option previously set is displayed in brackets and is the first to be displayed.
ND = Normally De-energised i.e.: Output is not energised until an alarm occurs. NE = Normally energised i.e.: Output is energised and then is de-energised once an alarm occurs. IFS-2600 Installation & Programming Manual Then relay #1 would be set as MAP OR with its mapping as (09) 00 00 00 00, relay #2 would be set as MAP OR with it’s mapping set as (10) 00 00 00 00 and so on all the way up to relay #64. Note: In example 2, zone number 64 is reached and there are still more relays to go. Page 36 DESCRIPTION OF ALARM ZONE TYPES Different zone types can be selected using the programming mode.
Each zone can be selected as any one of the following: Type Standard Latching Standard Latching Non Latching Non Latching Time Delay Time Delay Time Delay Time Delay Time Delay. IFS-2600 Installation & Programming Manual Page 37 TIME DELAY AZF The time delay AZF zone can be preset to any one of 6 time delays in the initial setup. This type of zone is used for AS1668 smoke detection zones. Zone timing etc is as per AS1668-1991. Example: Timer #1 = 60 seconds Once the first alarm is received, the alarm LED is turned on steady. Page 38 ZONE OUTPUT CONFIGURATIONS Once a zone has alarmed, its output functions as programmed to one of the following output types. Type Indicate Only Indicate, Bell Indicate, Bell, General Alarm Indicate, Bell, General Alarm, Ancillary Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1 Indicate, Bell, General Alarm, Ancillary, Brigade Relay #2 Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1, &.
IFS-2600 Installation & Programming Manual ALARM VERIFICATION FACILITY (AVF) Alarm verification (AVF) is a facility used to minimise false alarms. AVF only applies to the zones programmed for the AVF function. GLOBAL PROGRAMMABLE OPTIONS Operation is as follows: If a zone is programmed as AVF and it registers an alarm, no alarm functions are performed, if it is the first AVF zone in alarm.
Page 40 APPENDIX D ANCILLARY TRIP (ACF) The ancillary trip is used for the shutting down of air conditioning systems etc. In the event of a fire. GLOBAL PROGRAMMABLE OPTIONS The ancillary trip can be programmed as latching or non- latching depending on the application.
It call also be programmed as normally energised or normally de-energised. IFS-2600 Installation & Programming Manual RELAY OUTPUT MAPPING A total of 64 expansion relays can be fitted to the IFS-2600.
Each relay can be individually programmed to mimic any of the following; STANDARD OUTPUTS WHICH MAY BE MIMICED ANCILLARY OUTPUT (ACF) BRIGADE ALARM RELAY #1 BRIGADE ALARM RELAY #2. FAULT RELAY (NORMALLY ENERGISED). Page 42 FAULT/ISOLATE MAPPING FAULT/ISOLATE MAPPING works the same as OR mapping of alarm except it relates to the fault/isolate flag on each zone instead of the alarm flag. This function will cause the relay to operate if any one of up to five (5) zones go into fault/put in isolate.
If the relay map options are set as '01'. IFS-2600 Installation & Programming Manual GLOSSARY OF TERMS AS-4428.1 Australian standard for; - Automatic Fire Detection and Alarm Systems Control and Indicating Equipment. AS-4428.1 Australian standard for; - Automatic Fire Detection and Alarm Systems Power Supply Units. AS-1670 Australian standard for; - Automatic Fire Detection and Alarm Systems System Design Installation and Commissioning.
Page 44 IFS-2600 Installation & Programming Manual APPENDIX G SUMMARY OF TERMINATIONS AND CAUTIONS MCP LOOP Used for the looping of the manual call point to a particular zone chosen for indication. This is achieved by wiring from the zone, to the MCP, to the MCP loop then out to the field with the EOL across the last detector. The MCP is the first device on the circuit and both fault and alarm conditions will be indicated.
IFS-2600 Installation & Programming Manual BATTERY The 24V batteries are connected at these terminals. Damage to the equipment.
DOOR HOLDER AC INPUT Terminate the door holder AC transformer at these terminals. 24 VAC is the only acceptable power source at this point. Page 46 IFS-2600 Installation & Programming Manual APPENDIX H IFS-2600 PROGRAMMED OPTIONS Global System Parameters Date: Latch ND Non-Latch ND Latch NE Non-Latch NE ACF Output Disabled 2 min 3 min 4 min 5 min Alarm Verification (AVF) Notes: Programmed by Place an 'X'. IFS-2600 Installation & Programming Manual Page 47 ZONE TYPE PROGRAMMING Date: AZF No. STD STD N/L Place an 'X' in the appropriate box = Default P/N 10069 ECN08-0066. Page 48 IFS-2600 Installation & Programming Manual AZF No.
STD STD N/L Place an 'X' in the appropriate box = Default P/N 10069 ECN08-0066. IFS-2600 Installation & Programming Manual Page 49 ZONE OUTPUT PROGRAMMING Date: INDICATE IBG- IBGA- IBGA- BR2 IBGA- AZF No. BELL GENERAL BR1&BR2 Place an 'X' in the appropriate box = Default P/N 10069 ECN08-0066. Page 50 IFS-2600 Installation & Programming Manual INDICATE IBG- IBGA- IBGA- IBGA- AZF No. BELL GENERAL BR1&BR2 Place an 'X' in the appropriate box = Default P/N 10069 ECN08-0066.
IFS-2600 Installation & Programming Manual Page 51 RELAY OUTPUT MAPPING Date: MAPPING MAINS BELL ISO/ FAIL Place an 'X' in the appropriate box = Default P/N 10069 ECN08-0066. Page 52 IFS-2600 Installation & Programming Manual MAPPING MAINS BELL ISO/ FAIL P/N 10069 ECN08-0066. IFS-2600 Installation & Programming Manual Page 53 APPENDIX I TECHNICAL DRAWINGS MAIN KEYPAD AND DISPLAY EXPANSION DISPLAY P/N 10069 ECN08-0066. Page 54 Block Connection Diagram MAIN PROCESSOR BOARD IFS PCB2004 ZONE DISPLAYS 1-8 CABLE C3 16 ZONE DISP PCB816 MAINS SUPPLY 240 V AC 8 ZONE DISP PCB816 240V ISOL LAST DISPLAY CAN BE 8/16 OTHERS MUST BE 16 ZONE Copyright This document is &. IFS-2600 Installation & Programming Manual System Sensor Conventional Detector Connection Diagram DET A TO PANEL BASE B401 BASE A TO PANEL BASE B401R Copyright This document is & shall remain the property of Notifier Inertia Fire Systems Unauthorised use of this document in any way is prohibited. Page 56 Hochiki Conventional Detector Connection Diagram DET A TO PANEL DET A TO PANEL WHITE Copyright This document is & shall remain the property of Notifier Inertia Fire Systems Unauthorised use of this document in any way is prohibited.
Revision - revise on CAD. IFS-2600 Installation & Programming Manual Ancillary Connection Diagram NOTE: PCB1125 may be omitted if the In this case a 4K7 EOL must be IFS2600 TERMINATION PCB2004 1.5 OHM 5W FITTED WHEN STROBE USED TP 0V MAF ISO DATA 2600/DHTX DOOR HOLDER TRANSFORMER 240V/24V TRANSFORMER Copyright.
Page 58 ASE Connection Diagram IFS2600 TERMINATION PCB2004 Copyright This document is & shall remain the property of Notifier Inertia Fire Systems Unauthorised use of this document in any way is prohibited. =DocumentFullPathAndName Revision - revise on CAD. Do not amend by hand Eng. IFS-2600 Installation & Programming Manual Auto Changeover Dual Sounder Connection Diagram IFS2600 TERMINATION PCB2004 Copyright This document is & shall remain the property of Notifier Inertia Fire Systems Unauthorised use of this document in any way is prohibited. ADDED RELAY G.W.
Page 60 Auto Change Over Dual Sounder Connection Diagram IFS2600 TERMINATION PCB2004 ALERT ACTIVATION IFS803 RELAY BOARD EVAC ACTIVATION Copyright This document is & shall remain the property of Notifier Inertia Fire Systems Unauthorised use of this document in any way is prohibited. IFS-2600 Installation & Programming Manual MIMIC Connection Diagram IFS2600 TERMINATION BOARD TP 0V Max 120 Meters MAF ISO 4/0.75mm cable POWER AND SIGNAL RETURN MIMIC DATA SERIAL BUS Copyright This document is & shall remain the property of Notifier Inertia Fire Systems Unauthorised use of this document in any way is prohibited. Page 62 Single Fan Connection Diagram FIRE PANEL AUX POWER AUX +24 AUX 0V FAN START RELAY FAN STOP RELAY Copyright This document is & shall remain the property of Notifier Inertia Fire Systems Unauthorised use of this document in any way is prohibited. IFS-2600 Installation & Programming Manual Dual Fan Connection Diagram FIRE PANEL AUX POWER AUX +24 AUX 0V FAN 1 START RELAY FAN 1 STOP RELAY FAN 2 START RELAY FAN 2 STOP RELAY.NOTE FOR SINGLE CONTROL REMOVE SW2 LINK SW1 A & B TO SW2 A, B Copyright This document is &. Page 64 Exhaust Fan Connection Diagram FIRE PANEL AUX POWER AUX +24 AUX 0V FAN STOP RELAY (MAPPED TO ACF FOR GENERAL OR ZONED).
NOTE EITHER THE MAPPING ABOVE MAY BE USED TO STOP THE EXHAUST FAN OR THE GENERAL ACF TRIP BELOW, BUT NOT BOTH. IFS-2600 Installation & Programming Manual Supply Fan Connection Diagram FIRE PANEL AUX POWER AUX +24 AUX 0V FAN START RELAY (MAPPED TO ACF FOR GENERAL OR ZONED) FAN STOP RELAY (MAPPED TO AIR INTAKE SMOKE DETECTOR).
NOTE EITHER THE MAPPING ABOVE MAY BE USED TO START THE SAF OR THE GENERAL ACF TRIP BELOW, BUT NOT BOTH. Page 66 Smoke Spill Fan Connection Diagram FIRE PANEL AUX POWER AUX +24 AUX 0V FAN START RELAY (MAPPED TO ACF FOR GENERAL OR ZONED). NOTE EITHER THE MAPPING ABOVE MAY BE USED TO START THE SSF OR THE GENERAL ACF TRIP BELOW, BUT NOT BOTH. IFS-2600 Installation & Programming Manual 10W EVAC Connection Diagram IFS2600 TERMINATION BOARD LINK JP1 Copyright This document is & shall remain the property of Notifier Inertia Fire Systems Unauthorised use of this document in any way is prohibited. =DocumentFullPathAndName Revision - revise on CAD. Do not amend by hand Eng. Page 68 10W EVAC Slave Connection Diagram IFS2600 TERMINATION BOARD LINK JP1 Copyright This document is & shall remain the property of Notifier Inertia Fire Systems Unauthorised use of this document in any way is prohibited.
Revision - revise on CAD. Do not amend by hand Eng. IFS-2600 Installation & Programming Manual 30W EVAC Connection Diagram IFS2600 TERMINATION BOARD LINK JP1 +24V IFS1100 POWER SUPPLY 240V/20V TRANSFORMER Copyright This document is & shall remain the property of Notifier Inertia Fire Systems Unauthorised use of this document in any way is prohibited. Page 70 30W EVAC Slave Connection Diagram IFS2600 TERMINATION BOARD LINK JP1 +24V IFS1100 POWER SUPPLY 240V/20V TRANSFORMER Copyright This document is & shall remain the property of Notifier Inertia Fire Systems Unauthorised use of this document in any way is prohibited. IFS-2600 Installation & Programming Manual 50W EVAC Connection Diagram AUDIO TRANSFORMER IFS2600 TERMINATION BOARD LINK JP1 +24V MAINSON MFN/C MFN/O MFCOM LOWN/C LOWN/O LOWCOM Copyright This document is & shall remain the property of Notifier Inertia Fire Systems Unauthorised use of this document in any way is prohibited.
Page 72 50W EVAC Slave Connection Diagram AUDIO TRANSFORMER IFS2600 TERMINATION BOARD LINK JP1 +24V MAINSON MFN/C MFN/O MFCOM LOWN/C LOWN/O LOWCOM Copyright This document is & shall remain the property of Notifier Inertia Fire Systems Unauthorised use of this document in any way is prohibited. New South Wales Queensland 24 Potts Street (Head Office) East Brisbane, QLD 4169 7 Columbia Court Baulkham Hills NSW 2153 ph +61 (0)7 3391 5777 ph +61 (02 9899-4155 fax +61 (0)7 3391 5800 fax +61 (0)2 9899-4156 Western Australia Unit 4, 283 Camboon Road Malaga WA 6090 ph +61 (0)8 9270 6555.